330.30(B) Safeguarding.Cables must be fastened at intervals of no more than 1.8 meters, unless otherwise specified (6 ft). Cables having four conductors or fewer, no bigger than 10 AWG, must be fastened within 300 mm (12 in.)
Every outlet box, junction box, cabinet, or fitting must have Type MC cable with four or fewer conductors that are no greater than 10 AWG fastened within 12 inches of it, and at intervals no longer than six feet [330.30(B)].
Might as well think about using PVC for the entire run rather than MC if you're going to do that? Oh, and please remember not to place MC inside of EMT or PVC conduit. It is therefore not appropriate for damp environments. It is not permissible to put a non-waterproof wire or cable through a conduit in order to make it waterproof.
The Benefits of MC CableAccording to Article 330.30, the cable should essentially be supported every 6' and 12" before each box.
A great way to connect flexible metallic conduit, AC, MC, MCI-A, HCF, and NM cable to a steel outlet box or other enclosure is with Topaz's Combination Cable Connector, two screw Clamp type. It enables flexible cord and encased cable to be securely joined to outlet boxes and enclosures.
Art. 392 permits the installation of type MC cable in a cable tray. (2) Buried Directly. Direct-buried wires need to be safeguarded in line with Sec.
(1) For cables up to ¾ in. in external diameter, smooth-sheath Type MC cables cannot be bent in such a way that the bending radius of the inner edge of the cable is less than 10 times the external diameter of the metallic sheath. (B) A corrugated or interlocked sheath.
You can use 14/3 Armored MC Cable in dry or wet areas, indoors or out. The copper conductors that are soft-drawn are rated to withstand 600 volts. Ideal for usage in commercial, industrial, institutional, and multi-residential buildings as a feeder and service power distribution system.
The conductors are copper, 12 AWG. Bridle rings should only be used to bundle, stack, or hold up to 20 current-carrying conductors.
Section 334.30 of the codebook specifies that flat wires are to be stapled on their flat side rather than their edge. 2. This keeps the wire sheathing intact and ensures a tight wire connection to the stud.